Impact Window Test Results

Dade County
Association NOA
Unit Description Performance Design Pressure Test Pressure
3 1/4" CasementAir :<0.01 cfm/sq. ft.(1.57 psf, 25 mph)
Size : 32 "x 72"Water :DP 65(9.75 psf)
Annealed glassStructural :DP + 65, - 75(+ 97.5, -112.5 psf)
Impact & Cycling :DP + 65, - 75(+ 65, - 75 psf)
 
4 9/16 " CasementAir :<0.01 cfm/sq. ft.(1.57 psf, 25 mph)
Size : 32"x 72"Water :DP 65(9.75 psf)
Annealed glassStructural :DP + 65, - 75(+ 97.5, -112.5 psf)
Impact & Cycling :DP + 65, - 75(+ 65, - 75 psf)
 
3 1/4 " FixedAir :<0.01 cfm/sq. ft(1.57 psf, 25 mph)
Size : 48 "x 72"Water :DP 65(9.75 psf)
Annealed glassStructural :DP + 65, - 75(+ 97.5, -112.5 psf)
Impact & Cycling :DP + 65, - 75(+ 65, - 75 psf)
 
4 9/16 " FixedAir :<0.01 cfm/sq. ft(1.57 psf, 25 mph)
Size : 48"x 72"Water :DP 65(9.75 psf)
Annealed glassStructural :DP + 65, - 75(+ 97.5, -112.5 psf)
Impact & Cycling :DP + 65, - 75(+ 65, - 75 psf)
 
3 1/4" Double HungAir :<0.03 cfm/sq. ft(1.57 psf, 25 mph)
Size : 40 "x 72"Water :DP 65(9.75 psf)
Annealed glassStructural :DP + 65, - 70(+ 97.5, -105 psf)
Impact & Cycling :DP + 65, - 70(+ 65, - 70 psf)
 
3 1/4 " Single HungWater :<0.03 cfm/sq. ft(1.57 psf, 25 mph)
Size : 40 "x 72"Air :DP 65(9.75 psf)
Annealed glassStructural :DP + 65, - 70(+ 97.5, -105 psf)
Impact & Cycling :DP + 65, - 70(+ 65, - 70 psf)

Note: To comply with approvals, all product must be installed per Dade County product control notice of acceptance sheets. All windows used steel reinforcements and Sea-Storm laminated glass. Maximum allowable window combination width: 4 mulled units providing each individual unit width does not exceed the tested specimen width.